FCC/S 1.x.x.1: Is the basic load active if dew point and fill level alarm has triggered in cooling mode?

Marcel Feuerstein
04.07.2018 15:25

No! That would endanger the building. In this alarm state the basic load is off no matter what is parameterized or set via the bus. After the alarm has ended, the parameter / bus commands are executed again with bus commands also those that were set during the alarm.