IPR/S 3.5.1: How can I reset the IP Router Secure?

BA Engineering Team
02.09.2019 14:26

Resetting to factory settings can also be performed directly on the device. This is not a security risk, because the device will no longer be part of the system afterward.

  • Press the Programming button when the KNX bus is not connected.
  • Hold the Programming button down and plug on the bus terminal. The Programming LED flashes (2 Hz)
  • Press the button, hold it for at least 5 s and then release it. The Programming LED goes out, and the device reboots with the factory settings.

The Router can be reprogrammed if ETS connects with the device after reset and if the device’s FDSK is still known to ETS. ETS will report that the device was reset in this case.

Tags: Interface, KNX Secure, Remote Control
Average rating: 0 (0 Votes)

You cannot comment on this entry