What is the function of the „RESET-Button“ under the ABA/S 1.2.1 tag holder?
Short keypress (1sec-10sec):
ON-LED starts flashing and turns off shortly thereafter. After that the Logic Controller is doing a restart which means that the ON-LED starts flashing again. If this LED flashes permanent the restart was successful. This process lasts between 60-90 seconds.
Notice: If a running process was not quit correctly important datas can be lost.
Long keypress (>10sec): Caution factory reset!
ON-LED starts flashing and turns off shortly thereafter. After that the Logic Controller is doing a restart which ends with a permanent flashing ON-LED. Now the ABA/S is unloaded. This process lasts between 60-90 seconds.
Changes in the device:
- Reset of the physical address (15.15.255)
- Network settings and network properties are set on default
- Group addresses are deleted
- Address-, association- and group object table are also deleted