What is the function of the „RESET-Button“ under the ABA/S 1.2.1 tag holder?

Carolina Bachenheimer-Schaefer
21.11.2016 16:02

Short keypress (1sec-10sec):

ON-LED starts flashing and turns off shortly thereafter. After that the Logic Controller is doing a restart which means that the ON-LED starts flashing again. If this LED flashes permanent the restart was successful. This process lasts between 60-90 seconds.  

Notice: If a running process was not quit correctly important datas can be lost.

 

Long keypress (>10sec): Caution factory reset!

ON-LED starts flashing and turns off shortly thereafter. After that the Logic Controller is doing a restart which ends with a permanent flashing ON-LED. Now the ABA/S is unloaded. This process lasts between 60-90 seconds.

Changes in the device:

  • Reset of the physical address (15.15.255)
  • Network settings and network properties are set on default
  • Group addresses are deleted
  • Address-, association- and group object table are also deleted
  • Application program 1+2 = unloaded
Tags: KNX, TP