What room setpoint temperature is assumed during an ETS reset of the HCC/S 2.x.x.1?
This depends on the current mode of operation.
If the HCC is in heating mode, the value for the lower limit of the temperature band is taken (default: 20°C).
If the HCC is in cooling mode, the value for the upper limit of the temperature band is taken (default: 12°C).
Thus, the value closest to the room temperature is assumed. Further heating or cooling of the room is prevented.
Tags: ClimaECO, HVAC, KNX