FCC/S 1.x.x.1: What must be considered if analog room control unit is deactivated in the parameter “setpoint adjustment”?

Marcel Feuerstein
09.07.2018 14:06

Example:
Input a is set as window contact -> After that room control unit is activated in the setpoint adjustment. Right now “input a” is used as input for the control unit and not a window contact anymore. If room control unit is deactivated again (for any reason) “input a” is also set to window contact, again.

This is a feature of ETS!