How many thermoelectric valve drives can be connected to each VAA/S output?

Carolina Bachenheimer-Schaefer
09.02.2017 13:36

This depends on the maximum Inrush current of the valve drive and the operating current of the valve drive.

The maximum inrush current of the VAA/S is 300 mA for 2 min at Ts up to 60 °C per output.

Ts is the surrounding temperature.

The maximum operating current of the VAA/S is 160 mA at TS up to 45 °C per output.

Tags: KNX, TP, Valve Drive
Average rating: 0 (0 Votes)