Is the DIN 14676 standard for home smoke detectors fulfilled through the connection of smoke detector FC 650 to the GM/A?

Carolina Bachenheimer-Schaefer
06.10.2016 11:05

The connection of FC 650 detectors from the fire detector series to the GM/A does not fulfill the DIN 14676 standard for home smoke detectors. A home smoke detector must be able to signal an alarm independently of a central system. The FC 650 cannot acoustically signal an alarm on its own. A fire alarm is always evaluated and signaled in a central GM/A.