What can be the reason for a flashing ON-LED on the ABA/S 1.2.1?

Carolina Bachenheimer-Schaefer
21.11.2016 15:35

1. During the initialization of the logic controller. This means that the stack is being started -> After about 60-90 sec. ON LED = ON

2. In case of a power failure (Stack is still saved) -> After that ON-LED = OFF

3. Lost KNX-BUS connection (Telegram LED = OFF)

4. Aborted download

5. After a factory reset